How to specify custom linear lighting

Nine decisions, in the order that avoids rework, and what a complete schedule line looks like at the end.

Short answer

Specify custom linear lighting by deciding, in order: (1) the application and light-level targets, (2) mounting and ceiling type, (3) distribution and optic, (4) output in lumens per foot, confirmed by calculation, (5) CCT and CRI, (6) the run layout with lengths and corners, (7) voltage, driver and feeds, (8) controls and emergency, and (9) compliance and finish. Then write it as one complete schedule line per type so a supplier can quote it without guessing.

Key takeaways

  • Decide mounting and optic before output; they change the lumens you need.
  • Specify delivered lumens per foot, not LED chip lumens.
  • Draw the run layout; a length in a table is not enough for corners and feeds.
  • In Canada, state the input voltage (120, 277 or 347 V) and the certification mark required.

1. Application and targets

Write down the space type, the task, the target illuminance (horizontal and, for walls and retail, vertical), glare limits, and any owner standard. These set everything that follows.

2. Mounting and ceiling

Suspended, recessed (T-bar, drywall, trimless), surface or wall. Mounting affects housing, hardware, plenum depth and install sequence. See suspended, recessed and surface-mounted.

3. Distribution and optic

Direct, direct/indirect, or asymmetric (wall wash). Lens: opal for softness, microprismatic for lower glare, louvres for cutoff. The optic changes how much light reaches the task.

4. Output

Run a calculation with the product’s photometric (IES) file and set delivered lumens per foot. Note the resulting W/ft; it drives driver sizing and energy-code compliance.

5. Colour

CCT (for example 3000K, 3500K, 4000K) consistent with the rest of the project; CRI 80 minimum for general areas, 90+ where colour matters (retail, healthcare exam, hospitality). Specify colour consistency (for example 3-step MacAdam) for long continuous runs where sections sit side by side.

6. Run layout

Draw every run on the reflected ceiling plan with overall lengths, corners (L, T, X), patterns, and wall-to-wall conditions that need field verification. See continuous runs.

7. Voltage, drivers and feeds

State the input voltage: 347 V is common in Canadian commercial buildings, alongside 120 V and 277 V. Choose integral or remote drivers, mark feed points, and check driver loading (driver sizing) and, for low-voltage systems, 24V vs 48V.

8. Controls and emergency

Dimming protocol (0-10V, DALI, phase), dimming range (to 10% or 1%), control zones, daylight and occupancy requirements, and emergency (integral battery or central inverter).

9. Compliance and finish

A certification mark for Canada (for example CSA, cULus or cETLus), damp or wet location ratings, any energy-program listing needed for incentives, and the finish or colour.

Example schedule line

Field Example
Type L1
Description Suspended direct/indirect linear, continuous runs per plan
Mounting Aircraft cable, 18 in drop, power from canopy
Optic Microprismatic down, opal up; 30/70 up/down
Output 450 lm/ft delivered, max 4.5 W/ft
Colour 3500K, CRI 90, 3-step MacAdam
Lengths Per RCP; L-corners lit; field-verify wall-to-wall runs
Electrical 347 V input, integral drivers
Controls 0-10V dimming to 1%
Emergency Integral battery in marked sections
Finish Matte white
Basis of design Manufacturer X, catalogue …, or approved equal

The example is illustrative. Values must come from the project’s calculations.

Frequently asked questions

Should I specify a manufacturer or a performance spec?

Either works. A named basis-of-design product with “or approved equal” plus a clear performance requirement (delivered lumens, distribution, CCT, CRI, dimming range) gives the best balance of design control and competitive pricing.

What light levels should I design to?

Use the illuminance recommendations for the space type from the IES (Illuminating Engineering Society) and any owner standard, and check against the energy code’s lighting power limits. Offices are commonly designed to around 300–500 lux on the task plane.

References

  1. IES Lighting Handbook / recommended practices for illuminance by space type
  2. Ontario Building Code, SB-10 energy efficiency requirements — governing reference